The Defense Nuclear Facilities Safety Board (DNFSB) has raised concerns about the reliability of fire-water supplies at the Y-12 National Security Complex, citing blocked water-flow paths and the drinking-water system’s classification as general service despite supporting fire protection systems.
In a partly-redacted June 10 letter to Energy Secretary Chris Wright, published to the website Nov. 18, the board said Y-12’s fire protection program generally complies with Department of Energy and industry requirements, but the potable water system is classified as “general service” despite supplying safety-class and safety-significant fire protection systems. The board said that designation is inconsistent with DOE requirements for support systems.
The concern was highlighted by an event in February 2025, when Bechtel-led Y-12 contractor Consolidated Nuclear Security (CNS) discovered that two of three possible water-flow paths to a facility were blocked. The configuration created a single-point failure for the facility’s credited fire protection systems. During subsequent testing, personnel unintentionally isolated fire-water for about 12 minutes, with the issue not identified until more than a week later.
CNS has identified potential improvements, including remote pressure monitoring, stronger controls over critical water-flow paths, replacement of high-risk fire-water piping and improved tools for tracking valve positions. However, the board said CNS and the Y-12 Field Office had not committed to implementing the measures or incorporating them into facility or sitewide safety bases.
The board also identified other fire protection concerns, including deteriorating fire-resistant paint at a Y-12 facility, which it said could leave a roof fire capable of causing a total facility loss. A related safety analysis issue resulted in restrictions on roof hot work. Inspectors also found scaffolding obstructing sprinkler coverage and raised concerns about operating the potable water system with a single water tank.
The DNFSB recommended that DOE establish formal compensatory measures to improve potable water reliability and said it will continue overseeing Y-12’s corrective actions.